Product photo
Low Frequency UPS 10KVA-30KVA
HQ33 Series · Online Double Conversion · 3 Phase Input / 3 Phase Output · industrial backup power UPS with transformer.
Models: HQ3310L / HQ3320L / HQ3330L
Input
380/400/415VAC · 3 Phase + N + PE
Output
380/400/415VAC · 3 Phase + N + PE
Efficiency
≥93% @ 100% load
Transfer time
0 ms
| Parameter | Value |
|---|---|
| Series | HQ33 |
| Capacity | 10kVA / 20kVA / 30kVA |
| Topology | Online Double Conversion |
| Input rated voltage | 380/400/415VAC, 3 Phase + N + PE |
| Input voltage range | ±25% |
| Input rated frequency | 50/60Hz (Auto-sensing) |
| Input frequency range | 40–70Hz |
| Output rated voltage | 380/400/415VAC, 3 Phase + N + PE |
| Output voltage accuracy | ±1% |
| Transient response | ±5% < 10ms |
| Power factor | 0.9 |
| Phase voltage | 220V (200–244V configurable) |
| Crest factor | 3:1 |
| THDu | <2% @ 100% linear load; <5% @ 100% non-linear load |
| Bypass rated voltage | 380/400/415VAC |
| Bypass rated frequency | 50/60Hz |
| Bypass frequency range | ±10% (±5% configurable) |
| Inverter/Bypass switch | 0ms |
| Overload | 125%: 10 min; 150%: 1 min |
| Battery voltage | 360–408V (30–34 units configurable) · no neutral wire |
| Display | 7" touch screen |
| Communication | RS232, RS485, optional: dry contact, SNMP |
| Operating temperature | -10–40°C |
| Humidity | 0–95% (non-condensing) |
| Altitude | <1000m no derate; >1000m derating 1% per 100m |
| Noise | ≤65dB @ 1m |
| Minimum order | 80 |